40 MW Hyperscale Data Center — Reactive Support & UPS Input Power Quality
Three 2.4 MW UPS modules running in parallel at a 40 MW hyperscale facility were circulating rectifier harmonics between units — unbalancing load sharing, thermally stressing the battery strings and triggering false PDU alarms. Three ASVG-150kvar units went in on the LV bus, with AHF-200A units at the UPS input. Distortion at the UPS input fell from 14.0% to 2.8%, circulating current dropped by 80%, and the site recovered 2.6M CNY in annual energy cost.
THD 14.0% → 2.8% · circulating current down 80% · 2.6M CNY saved per year